Single Mode 12F MPO APC to LC Fanout Patch Cord / MTP APC to LC Harness Cable SMF 12fibers
Single Mode 12F MPO APC to LC Fanout Patch Cord / MTP APC to LC Harness Cable SMF 12fibers Structure:
Structure:
Connector Side A + Main Cable + Connector Side B
MPO APC / MTP APC 12F SM G657 Mini Cable 3.0mm LC/UPC Duplex
Single Mode 12F MPO APC to LC Fanout Patch Cord / MTP APC to LC Harness Cable SMF 12fibers Structure:
- MPO APC to LC / MTP APC to LC 12F breakout cable maps a single 12-fiber MPO / MTP connector into 6 duplex LC connectors.
- The polarity method of these cables dictates how the Transmit (TX) and Receive (RX) lines are routed between the two ends. There are 3 types of polarities as below:
+ Polarity Type A (Straight-Through)
Pin Mapping: Fiber 1 on the MPO connector connects to Fiber 1 on the LC connector, Fiber 2 to Fiber 2, and so on.
Key Alignment: Uses a Key-Up to Key-Down configuration.
Use Case: Primarily used to connect to pre-terminated backbone trunks in standard, modular cassette deployments. Because LC ports are duplex (TX/RX), you will need to "cross" the TX/RX with a standard A-to-B patch cord on one end to ensure the signal reaches the network receiver.
+ Polarity Type B (Crossed / Rollover)
Pin Mapping: Fiber 1 on the MPO connects to Fiber 12 on the LC side, Fiber 2 to Fiber 11, and so on.
Key Alignment: Uses a Key-Up to Key-Up configuration.
Use Case: This is the most common method for direct transceiver-to-transceiver connections (e.g., 40G/100G parallel optics) and breakout applications, as it provides the correct TX-to-RX flip internally.
+ Polarity Type C (Pair-Swapped)
Pin Mapping: Pairs of fibers are flipped; Fiber 1 on the MPO maps to Fiber 2 on the LC, Fiber 2 maps to Fiber 1, and so on.
Key Alignment: Uses a Key-Up to Key-Up configuration.
Use Case: Typically used for pairwise swapped structured cabling directly to LC duplex channels, though it is less common for modern parallel optics.
12F MPO/APC MTP/APC Connector
Detail Ordering Information
- Side A connector:
MPO/APC 12F,
MTP/APC 12F
- Side A connector:
Male
Female
- Cable: Single Mode G657A1 micro high-density cable 3.0mm
- Fiber count: 12fo
- Sice B connector:
LC UPC Duplex
LC UPC Unitboot Duplex
- Fanout diameter: 2.0mm
- Fanout length: 30cm, 50cm
- Length: customized
- Polarity: Type A, Type B, Type C
- Insertion Loss: Elite (ULL), Standard.
- Label: customized
- Quantity: MOQ 1pc
Applications
+ FTTx (FTTA, FTTB, FTTC, FTTH, FTTO, etc)
+ Data Center Interconnection
+ WAN/LAN
+ High-speed railway station control room
+ AI data center
+ Star-link data center
+ Bank data center
Specifications
|
Type |
Single Mode |
Single Mode |
Multi Mode |
|||
|
(APC Polish) |
(UPC Polish) |
(PC Polish) |
||||
|
Fiber Count |
8f,12f, 16f, 24f, 32f, 48f |
8f,12f, 16f, 24f, 32f, 48f |
8f,12f, 16f, 24f, 32f, 48f |
|||
|
Fiber Type |
G657A1, G657A2 |
G657A1, G657A2 |
OM1,OM2,OM3, OM4, OM5, etc. |
|||
|
Max. Insertion Loss |
Elite |
Standard |
Elite |
Standard |
Elite |
Standard |
|
Ultra Low Loss |
Ultra Low Loss |
Low Loss |
||||
|
≤0.35 dB |
≤0.75dB |
≤0.35 dB |
≤0.75dB |
≤0.35 dB |
≤0.60dB |
|
|
Return Loss |
≥60 dB |
≥60 dB |
NA |
|||
|
Durability |
≥500 times |
≥500 times |
≥500 times |
|||
|
Operating Temperature |
-40℃~+80℃ |
-40℃~+80℃ |
-40℃~+80℃ |
|||
|
Test Wavelength |
1310nm |
1310nm |
1310nm |
|||
|
Insert-pull test |
1000 times<0.5 dB |
|||||
|
Interchange |
<0.5 dB |
|||||
|
Anti-tensile force |
15kgf |
|||||