SM G657 MPO APC to LC Fan-out 24F Patch Cord / Mono mode 24fibers MTP APC to LC Harness Cable Type B
MPO APC to LC Fan-out 24F Patch Cord / Mono mode 24fibers MTP APC to LC Harness Cable
Structure:
Connector Side A + Main Cable + Connector Side B
MPO APC / MTP APC 24F SM G657 Mini Cable 3.0mm LC/UPC Duplex
24F MPO to LC / MTP to LC harness cable polarity
- For a 24F MPO to LC harness cable / MTP to LC harness cable, the mapping depends on whether you are using a standard Type A, Type B, or Type C polarity.
- The most common configuration is Type B (Rollover), which maps Pin 1 on the MPO connector to Channel 12 on the LC side, and Pin 2 to Channel 11.
- The exact polarity mapping depends on the structured cabling standard (TIA-568) you are following:
+ Type A (Straight-Through): Fiber 1 connects to Fiber 1, Fiber 2 to Fiber 2, and so on. To ensure proper Transmit-to-Receive (Tx-to-Rx) alignment, one end of the link requires a standard crossover patch cord (A-to-B).
+ Type B (Reversed/Rollover): Fiber 1 connects to Fiber 24, Fiber 2 to Fiber 23, and so on. This method is highly popular for direct hardware patching (such as 40G/100G transceivers) as it seamlessly flips Tx and Rx automatically.
+ Type C (Pairwise Swapped): Adjacent fiber pairs are swapped (e.g., 1↔2, 3↔4, 5↔6). This maintains standard Tx/Rx alignment without needing crossover patch cables, but requires carefully configured trunk cables.
24F MPO APC / MTP APC Connector
Detail Ordering Information
- Side A connector:
MPO/APC 24F,
MTP/APC 24F
- Side A connector:
Male
Female
- Cable: Single Mode G657A1 micro high-density cable 3.0mm
- Fiber count: 24fo
- Sice B connector:
LC UPC Duplex
LC UPC Unitboot Duplex
- Fanout diameter: 2.0mm
- Fanout length: 30cm, 50cm
- Length: customized
- Polarity: Type A, Type B, Type C
- Insertion Loss: Elite (ULL), Standard.
- Label: customized
- Quantity: MOQ 1pc
Applications
+ FTTx (FTTA, FTTB, FTTC, FTTH, FTTO, etc)
+ Data Center Interconnection
+ WAN/LAN
+ High-speed railway station control room
+ AI data center
+ Star-link data center
+ Bank data center
Specifications
|
Type |
Single Mode |
Single Mode |
Multi Mode |
|||
|
(APC Polish) |
(UPC Polish) |
(PC Polish) |
||||
|
Fiber Count |
8f,12f, 16f, 24f, 32f, 48f |
8f,12f, 16f, 24f, 32f, 48f |
8f,12f, 16f, 24f, 32f, 48f |
|||
|
Fiber Type |
G657A1, G657A2 |
G657A1, G657A2 |
OM1,OM2,OM3, OM4, OM5, etc. |
|||
|
Max. Insertion Loss |
Elite |
Standard |
Elite |
Standard |
Elite |
Standard |
|
Ultra Low Loss |
Ultra Low Loss |
Low Loss |
||||
|
≤0.35 dB |
≤0.75dB |
≤0.35 dB |
≤0.75dB |
≤0.35 dB |
≤0.60dB |
|
|
Return Loss |
≥60 dB |
≥60 dB |
NA |
|||
|
Durability |
≥500 times |
≥500 times |
≥500 times |
|||
|
Operating Temperature |
-40℃~+80℃ |
-40℃~+80℃ |
-40℃~+80℃ |
|||
|
Test Wavelength |
1310nm |
1310nm |
1310nm |
|||
|
Insert-pull test |
1000 times<0.5 dB |
|||||
|
Interchange |
<0.5 dB |
|||||
|
Anti-tensile force |
15kgf |
|||||